Manual: Xmtk-9000 User
Insert the unit into the panel opening and secure it with the provided mounting brackets.
To configure system variables, you must access the password-protected engineering menu: Press and hold the key for three seconds. xmtk-9000 user manual
Routine preventative maintenance ensures the extended operational lifespan of your XMTK-9000 controller. Routine Maintenance Tasks Insert the unit into the panel opening and
The XMTK-9000 series is an intelligent industrial process controller designed for measurement, regulation, and control of key parameters such as temperature, pressure, flow, and liquid levels. This series features several key characteristics: Routine Maintenance Tasks The XMTK-9000 series is an
| Parameter | Specification | |-----------|---------------| | | 0–400°C (depending on sensor) | | Accuracy | ±0.5% FS ± 1 digit | | Display | 3½ digit 0.5-inch (or 0.8-inch) LED | | Input Types | Thermocouple (K, E, J, S, B, R, N, T), RTD (Pt100, JPt100), voltage (0–5V, 1–5V), current (0–10mA, 4–20mA) | | Sampling Cycle | 0.5 seconds | | Control Output | Relay 250VAC 5A, SSR driver 0–12V, current 0–10mA/4–20mA, voltage 0–5V/1–5V | | Alarm Output | Up to 2 groups, 12 modes, 250VAC 3A | | Power Supply | 220VAC ±10%, 50Hz | | Power Consumption | <10VA | | Panel Cutout | 45×45mm (common for 48×48mm housing) | | Operating Environment | 0–50°C, 35–85%RH, non-corrosive, non-condensing | | Weight | Approx. 0.2–0.5kg |